Helios II Series Power Inverter's capacitance bulged or exploded
Model
Helios II Series off grid solar inverter
Description
If the input voltage of battery exceeded defult value, capacitance will bulge/explode and further damage DC input part MOS tube.
Fault Causes
The input voltage of DC battery was too high.
Solutions and steps:
Change capacitance and MOS tube.
PS:
Battery voltage of all models of inverter should not exceed values below:
B12P--15.5V、B24P--31V、B48P--62V
Related Articles
Power inverter AC output part Mosfet/IGBT module exploded
Model BP series pure sine wave inverter Description AC output part MOS tube/ IGBT module exploded. AC output part driver board, corresponding resistances and PCB board were damaged. Fault Causes AC output was connected with grid. Solutions and steps ...
Helios II Series Off Grid Solar Inverter Charging Test
Model Helios II Series Off Grid Solar Inverter 1. Check the system parameter settings, "Forbid mains charging" is not selected in the main options, as shown in the picture below. 2.Check whether the fuse at the mains input terminal is intact, and ...
How will the inverter be affected if the input voltage is too high?
Model BP series/BPlus series/Helios Description If the input voltage of battery exceeded defult value, capacitance will bulge/explode and further damage DC input part MOS tube. Analysis of the possibility of the cause The input voltage of DC battery ...
HeliosII can not be turned on to detect
Model Helios II series off grid solar inverter First, after the normal all-in-one machine is turned on, you can hear the sound of the relay suction, the CPU board indicates that the red light is on, the display lights up and accompanied by a buzzer ...
2000W power inverter front-end MOS tube and fuse exploded
Model BP series pure sine wave inverter 2000W 48VDC 220VAC Description Front-end MOS tube and fuse exploded. Analysis of the possibility of the cause 1. Positive and negative of the battery power is opposite. 2. Or Battery voltage is too high. ...