HeliosII-485MCP off grid solar inverter has no vac output and the error code is DCBUS-L

HeliosII-485MCP off grid solar inverter has no vac output and the error code is DCBUS-L

Model

HeliosII-485MCP off grid solar inverter


Description

Inverter has no AC output and the error code is DCBUS-L.




Analysis of the possibility of the cause

Customer connected on the output other voltage engine generstor.


Solutions and steps

Check:
As illustrated in above image, the place marked by red box is the actual location of IPM module. The four points within the red ellipse are the points we need to measure. 
Measurement procedures: measure  IPM module-using  multimeter,  and discharge white capacitance at first.



1. Use black probe to connect 0 point, and use red probe to connect 1, 2, 3 point respectively. The value of measurement should be more than 500 normally.




2. Change black probe and red probe connection points, use red probe to connect 0 point, and using black probe respectively connect 1, 2, 3 point, the value should be 1, under normal condition as shown below. In another words, exceeding multimeter’s measurement range. 



If check all display 0V, means AC output part Mosfet (IPM Module) damaged.


Solutions:

1. Send back to factory to check.

2. Change the Mosfet.


    • Related Articles

    • Helios II Series Off Grid Solar Inverter Charging Test

      Model Helios II Series Off Grid Solar Inverter ​ 1. Check the system parameter settings, "Forbid mains charging" is not selected in the main options, as shown in the picture below. 2.Check whether the fuse at the mains input terminal is intact, and ...
    • Power inverter AC output part Mosfet/IGBT module exploded

      Model BP series pure sine wave inverter Description AC output part MOS tube/ IGBT module exploded. AC output part driver board, corresponding resistances and PCB board were damaged. Fault Causes AC output was connected with grid. Solutions and steps ...
    • Helios II Series Power Inverter's capacitance bulged or exploded

      Model Helios II Series off grid solar inverter Description If the input voltage of battery exceeded defult value, capacitance will bulge/explode and further damage DC input part MOS tube. Fault Causes The input voltage of DC battery was too high. ...
    • Inverter damaged AC output part mosfet caused by overload

      Model BPlus Series pure sine wave inverter Description The inverter still ran even after short circuit because of a full load in AC output, which damaged AC output part MOS tube. Fault Causes The inverter still overloaded after short ...
    • Output voltage is unsteady of BPlus Series 300W inverter

      Model BPlus series pure sine wave inverter  300W 12VDC 220VAC Description The inverter can be started up but its output voltage is unsteady. Analysis of the possibility of the cause R18 resistance in bus voltage has been damaged, the transient ...