HeliosII-485MCP off grid solar inverter has no vac output and the error code is DCBUS-L

HeliosII-485MCP off grid solar inverter has no vac output and the error code is DCBUS-L

Model

HeliosII-485MCP off grid solar inverter


Description

Inverter has no AC output and the error code is DCBUS-L.




Analysis of the possibility of the cause

Customer connected on the output other voltage engine generstor.


Solutions and steps

Check:
As illustrated in above image, the place marked by red box is the actual location of IPM module. The four points within the red ellipse are the points we need to measure. 
Measurement procedures: measure  IPM module-using  multimeter,  and discharge white capacitance at first.



1. Use black probe to connect 0 point, and use red probe to connect 1, 2, 3 point respectively. The value of measurement should be more than 500 normally.




2. Change black probe and red probe connection points, use red probe to connect 0 point, and using black probe respectively connect 1, 2, 3 point, the value should be 1, under normal condition as shown below. In another words, exceeding multimeter’s measurement range. 



If check all display 0V, means AC output part Mosfet (IPM Module) damaged.


Solutions:

1. Send back to factory to check.

2. Change the Mosfet.


    • Related Articles

    • The lighting fixture connected to the inverter's output terminal is damaged

      Model Helios II series off grid solar inverter 485MCP Description The inverter cannot be turned on, and the lighting fixture connected to the output terminal is damaged. Analysis of the possibility of the cause 1.After disassembly and inspection, it ...
    • HeliosII can not be turned on to detect

      Model Helios II series off grid solar inverter First, after the normal all-in-one machine is turned on, you can hear the sound of the relay suction, the CPU board indicates that the red light is on, the display lights up and accompanied by a buzzer ...
    • Helios II Series Off Grid Solar Inverter Charging Test

      Model Helios II Series Off Grid Solar Inverter ​ 1. Check the system parameter settings, "Forbid mains charging" is not selected in the main options, as shown in the picture below. 2.Check whether the fuse at the mains input terminal is intact, and ...
    • The BP 2500W inverter did not output and had smell of burnt

      Model BP series pure sine wave inverter 2500W 24VDC 220VAC Description The inverter did not output and had smell of burnt. After opening, DC input part MOS tube and fuse exploded, and DC input control board was damaged. Analysis of the possibility of ...
    • No output after running 2-3 months of BP 2000 watt power inverter

      Model BP series pure sine wave inverter 2000W 12VDC 220VAC Description No output after using for 2-3 months, red and blue light are on at same time.  Analysis of the possibility of the cause 1.The ambient temperature and humidity of the inverter is ...